Fluke 1621 Earth Ground Tester

Fluke 1621 Earth Ground Tester

Category: FLUKE

Specifications
Details

Earth Ground Tester for Resistance Measurement

The Fluke 1621 is an easy-to-use earth ground tester. For ground resistance testing, the 1621 is the first line of defense in detecting reliable ground connections. The unit features basic ground testing methods including 3-pole Fall-of-Potential as well as 2-pole ground resistance tests. Its convenient size, rugged holster, and large, clear LCD display make it an ideal field earth ground tester, for most electrical grounding work environments. With a simple user interface and intuitive functionality, the Fluke 1621 is a handy grounding tool for electrical contractors, utility test engineers, and earth ground specialists.

General Specifications

Measuring Functions 3-pole earth ground resistance, 2-pole AC resistance of a conductor, interference voltage
Intrinsic Error Refers to the reference temperature range and is guaranteed for one year
Measuring Rate 2 measurements/second
Battery One 9V alkaline (LR61)
Battery Condition LO-BAT displayed if voltage drops below 6.5V
Voltages Between jacks H/C2 and E/C1: 250 Veff max
Between jacks S/P2 and E/C1: 250 Veff max
Climatic Class VDE/VDI 3540 RZ (conforming to KWG as per DIN 40040, 4/87)
Temperature Performance Working: -10°C to +50°C (+14°F to +122°F)
Operating: 0°C to +35°C (+32°F to +95°F)
Storage: -20°C to +60°C (+68°F to +140°F)
Reference: +23°C ±2°C (+73°F ±4°F)
Temperature Coefficient ±0.1% of range per degree Kelvin
Safety IEC/EN 61010-1, 600V CAT II, pollution degree 2
Dimensions 113 × 54 × 216 mm (4.5 × 2.1 × 8.5 in), including holster
Weight 850 g (1.9 lb), including standard accessories (approx. 600 cm³ volume)
Note [1] Remove the battery for long-term storage to prevent leakage damage.
[2] The four temperature ranges satisfy European Standards; use the temperature coefficient to determine accuracy at any ambient temperature.

Electrical Specifications

Maximum Deviations (Influence Factors) E₁ Position – 0%
E₂ Supply Voltage – 0%
E₃ Temperature – 2.3%
E₄ Serial Interference Voltage (20V) – 0.6%
E₅ Probe and Auxiliary Probe Resistance – 10%
Test Voltage 3.7 kV
Protection Type IP40 (IEC/EN 60529)
Electromagnetic Compatibility Emission: IEC/EN 61326 Class B
Immunity: IEC/EN 61326 Annex C
RE Resistance Measurement Measuring method: Current-voltage with improved cross-talk attenuation, 3-pole or 2-pole (IEC/EN 61557-5)
Open circuit voltage: 23–24V AC
Short circuit current: >50 mA AC
Measuring frequency: 128 Hz
Maximum overload: 250 Veff
Measuring Time Approx. 8 seconds (average after START pressed)
Limit Input Tester retains set value even when turned off (if sufficient battery power)
Automatic Changeover of Resolution RH < 7 kΩ – Resolution 0.01 Ω
RH < 50 kΩ – Resolution 0.1 Ω
RH > 50 kΩ – Resolution 1 Ω
Interference Voltage Display (DC + AC) Vmax: 30 Veff
Common mode rejection: >80 dB at 50/60 Hz
Ri: 680 kΩ
Measuring uncertainty: <10% for pure AC and DC signals

Measuring Range

Range Resolution / Display / Accuracy
0.15 Ω to 20 Ω Resolution: 0.01 Ω
Display range: 0–19.99 Ω
200 Ω Resolution: 0.1 Ω
Display range: 20–199.9 Ω
2 kΩ Resolution: 1 Ω
Display range: 200–1999 Ω
Intrinsic Uncertainty ±(6% of measured value + 5D)
Operating Uncertainty IEC 61557 ±(18% of measured value + 5D)
Notes [1] Covers all deviations caused by influence quantities E₁–E₅.
If deviation E₄ (probe resistance) is higher than specified, readings flash.
Measured values may be outside the specified operating uncertainty.
 

View more about Fluke 1621 Earth Ground Tester on main site